The Worst Type Of Three Phase Faults (And Why It Happens)

When three phase fault occur

In a three phase power system, the type of faults that can occur are classified by the combination of conductors or buses that are faulted together.In addition, faults may be classified as either bolted faults or faults that occur through some impedance such as an arc.  


Four types of Three Phase Faults

1. Three Phase bolted faults
2. Bolted line to line faults
3. Line to line to ground faults
4. Line to ground faults

1. Three Phase Bolted Faults
A three phase bolted fault describes the condition where the three conductors are physically held together with zero impedance between them, just as if they were  bolted together. For balanced symmetrical system, the fault current magnitude is balanced equally within the three phase.

While this type of fault does not occur frequently, its results are used for protective device selection, because this fault type generally yields the maximum short circuit current value.
2. Bolted Line to line Faults
Bolted line to line faults are more common than three phse faults and have fault current that are approximately 87% of the three phase bolted fault current.

3. Line to line to Ground Faults
Line to line to ground faults are typically line to ground faults that have escalated to include a second phase conductor. This is an unbalanced fault. The magnitudes of double line to ground fault currents are usually greater than those of line to line faults, but are less than those three phase faults.
4. Line to Ground Faults
Line to ground faults are most common type of faults and are usually the lease disturbing to the system. The current in the faulted phase can range from near zero to a value slightly greater than the bolted three phase fault current. 













18 Initial Checks Of Electrical Installations Every Electrician MUST Perform

electrical installations

Testing of Electrical Installation 

Before any testing of low voltage electrical installations (and equipment) is carried out, a detailed physical inspection must be made to ensure that everything is:
1. To a relevant National or Harmonized European Standard
2. Erected/installed in compliance with the IEE Regulations 
3. Not damaged in such a way that it could cause danger

General Testing Checklist

1.Connections of Conductors
Are terminations electrically and mechanically sound ? Is installation and sheathing removed only to a minimum to allow satisfactory termination ?

2.Identification of Conductors
Are conductors correctly identified in accordance with the regulations?
identification of conductors

3.Routing of Cables
Are cables installed such that account is taken of external influences, such as mechanical damage, corrosion and heat?

4.Conductor Selection
Are conductors selected for current carrying capacity and voltage drop in accordance with the design?

5.Connection of single pole device
Are single pole protective and switching devices connected in the line conductor only?
connection of single pole device

6.Accessories and equipment
Are all accessories and items of equipment correctly connected?

7.Thermal effects
Are fire barriers present where required and protection against thermal effects provided ?

8. Protection against shock
What methods have been used to provide protection against electrical shock ?

9.Mutual detrimental influence
Are wiring systems installed so that they can have no harmful effect on non-electrical system or so that system of different currents or voltages are segregated where necessary ?